ISO Group Logo
Defense and Aerospace
Supply Chain Partner
A Dynatech International Company


NSN 5925-00-238-5145, 5925002385145
CIRCUIT BREAKER

Federal Supply Classification
FSC 5925 - Circuit Breakers
National Item Identification Number
NIIN 002385145
Codification Country
United States
Item Name Code
INC 00136
Criticality
(X) This item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Hazardous Material Indicator Code
(P) There is no information in the HMIRS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Availability: Request Qualified Suppliers: Currently qualifying suppliers

Manufacture or supply this part?
Join our growing community of certified suppliers.

Let Us Know
  CALL ABOUT NSN 5925-00-238-5145
Our client representatives are standing by to help fulfill your request.

+1-321-773-5710

  REQUEST QUOTE for 5925-00-238-5145


Have a list that needs to be quoted? Upload it here.

DLMS® Summary

National Stock Number 5925-00-238-5145

National Stock Number (NSN) 5925-00-238-5145, or NIIN 002385145, (circuit breaker) was assigned June 3, 1973 in the Federal Logistics Information System (FLIS). This NSN does not replace any other NSNs.

There are 4 manufacturer part numbers associated with this NSN. One of those part number(s) are considered obsolete. The manufacturer part numbers were originally supplied by 4 suppliers. Today, 3 suppliers are listed as Active suppliers for this NSN. Of the active suppliers, 2 suppliers are deemed design controlled or valid supply parts.

This part number has not been procured by the US Government in over 5 years.

Based on a planned procurement review by the Primary Inventory Control Activity (PICA) on Apr 02, 2006, this NSN's acquisition method was noted as: Suitable for Competitive Acquisition. (Potential sources shall include dealers/distributors.) This part requires engineering source approval by the design control activity in order to maintain the quality of the part. An alternate source must qualify in accordance with the design control activity's procedures, as approved by the cognizant Government engineering activity. Valid AMCs: 1, 2, 3, 4 and 5.

This NSN is assigned to Item Name Code (INC) 00136. [A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES:CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.]. This item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. There is no information in the HMIRS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product. NSN 5925002385145 does not contain precious metals.

This information was last updated on .


Technical Characteristics

MOUNTING SURFACE TO TERMINAL END DISTANCE
(AJWX) 1.835 INCHES MINIMUM AND 1.845 INCHES MAXIMUM
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE
(CPLM) 1.0 AMPERES AC FIRST LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE
(CPLM) 8.0 AMPERES AC SECOND LOCATION
CIRCUIT PROTECTION TYPE
(CPRH) OVERCURRENT ALL LOCATIONS
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT
(CPRY) ONE AND TWO LINKED
UNABLE TO DECODE
(ADTV) UNABLE TO DECODE
MOUNTING FACILITY TYPE AND QUANTITY
(AXHR) 4 THREADED HOLE
THREAD QUANTITY PER INCH
(CMLP) 32
MANUAL ACTUATOR TYPE AND QUANTITY
(CPRT) 2 TOGGLE
INTERNAL TRIP RELEASE CONFIGURATION
(CPSM) SERIES TRIP ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED
(CQXF) DUSTPROOF
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH
(AEBP) 1.555 INCHES MINIMUM AND 1.565 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH
(AEBY) 1.655 INCHES MINIMUM AND 1.665 INCHES MAXIMUM
MAIN CONTACT TRIPPING MECHANISM TYPE
(CPRR) TRIP FREE
ACTUATOR FUNCTION
(CPRW) TRIP-RESET
CASE MATERIAL
(CWJK) PLASTIC
BODY LENGTH
(ADAQ) 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM
NOMINAL THREAD SIZE
(CQJX) 0.138 INCHES
BODY WIDTH
(ADAT) 1.468 INCHES MINIMUM AND 1.532 INCHES MAXIMUM
CASE MATERIAL
(ADTV) PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH
(AEBQ) 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM
POLE QUANTITY
(AKPX) 2
TRIP RELEASE CHARACTERISTIC
(CPRL) TIME DELAY ALL LOCATIONS
ACTUATOR POSITION DESIGNATION
(CPRX) AT EACH POLE
THREAD SERIES DESIGNATOR
(THSD) UNC
ARC QUENCHING METHOD
(APNQ) MAGNETIC BLOWOUT
STORAGE TYPE
(BBRG) GENERAL PURPOSE WAREHOUSE
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT
(CQWN) 0.150 MINIMUM AT 200 PCT AND 0.300 MAXIMUM AT 200 PCT ALL LOCATIONS
FREQUENCY IN HERTZ
(FREQ) 60.0 ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS
(CPRF) 250.0 AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS
(CPRG) 1000.0 AC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT
(CPRN) 125.0 ALL LOCATIONS
TERMINAL TYPE AND QUANTITY
(TTQY) 4 TAB, SOLDER LUG
BODY STYLE
(AAQL) MULTIPOLE-MULTIPLE ACTUATOR TYPE
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH
(AEHA) 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM
FRAGILITY FACTOR
(AFJN) MODERATELY RUGGED
BOSS HEIGHT
(AJEC) 0.125 INCHES MINIMUM AND 0.135 INCHES MAXIMUM
TRIP RELEASE METHOD
(CPRJ) MAGNETIC-HYDRAULIC ALL LOCATIONS
RESET METHOD
(CPRQ) MANUAL
III FRAGILITY FACTOR
(AFJN) MODERATELY RUGGED

Manufacturer Part Numbers


Related Inventory



 
Top