NSN 5925-00-890-9731, 5925008909731
CIRCUIT BREAKER

Federal Supply Classification
FSC 5925 - Circuit Breakers
National Item Identification Number
NIIN 008909731
Codification Country
United States
Item Name Code
INC 00136
Criticality
(X) This item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Hazardous Material Indicator Code
(P) There is no information in the HMIRS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Availability: Readily Available Qualified Suppliers: Currently qualifying suppliers

Manufacture or supply this part?
Join our growing community of certified suppliers.

Let Us Know
  CALL ABOUT NSN 5925-00-890-9731
Our client representatives are standing by to help fulfill your request.

+1-321-773-5710

  REQUEST QUOTE for 5925-00-890-9731


Have a list that needs to be quoted? Upload it here.

DLMS® Summary

National Stock Number 5925-00-890-9731

National Stock Number (NSN) 5925-00-890-9731, or NIIN 008909731, (circuit breaker) was assigned April 17, 1968 in the Federal Logistics Information System (FLIS). NIIN 008909731 was cancelled on November 19, 2016, with a cancelled status of "Item is Cancelled - USE." This NSN was replaced by NSN 5925010376881. This NSN does not replace any other NSNs.

There are no manufacturer part numbers associated to this NSN.

This part number has not been procured by the US Government in over 5 years.

This NSN is assigned to Item Name Code (INC) 00136. [A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES:CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.]. This item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. There is no information in the HMIRS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product. NSN 5925008909731 does not contain precious metals.

This information was last updated on .


Technical Characteristics

MOUNTING SURFACE TO TERMINAL END DISTANCE
(AJWX) 1.828 INCHES MAXIMUM
BUSHING LENGTH
(ABXD) 0.380 INCHES MAXIMUM
BODY WIDTH
(ADAT) 1.281 INCHES MAXIMUM
CASE MATERIAL
(ADTV) METAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH
(AEBP) 0.906 INCHES MAXIMUM
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS
(CPRG) 500.0 DC ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE
(CPRR) TRIP FREE
BODY STYLE
(AAQL) MULTIPOLE-SINGLE ACTUATOR TYPE
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH
(AEBQ) 0.625 INCHES NOMINAL
POLE QUANTITY
(AKPX) 2
TRIP RELEASE CHARACTERISTIC
(CPRL) TIME DELAY ALL LOCATIONS
THREAD QUANTITY PER INCH
(CMLP) 32
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS
(CPRF) 50.0 DC ALL LOCATIONS
ACTUATOR POSITION DESIGNATION
(CPRX) AT EACH POLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE
(CPLM) 500.0 MILLIAMPERES DC ALL LOCATIONS
TRIP RELEASE METHOD
(CPRJ) MAGNETIC ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED
(CQXF) FUNGUS RESISTANT AND HERMETICALLY SEALED
MOUNTING FACILITY TYPE AND QUANTITY
(AXHR) 1 THREADED BUSHING
CIRCUIT PROTECTION TYPE
(CPRH) OVERCURRENT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT
(CPRN) 125.0 ALL LOCATIONS
ACTUATOR FUNCTION
(CPRW) TRIP-RESET
INTERNAL TRIP RELEASE CONFIGURATION
(CPSM) SERIES TRIP ALL LOCATIONS
NOMINAL THREAD SIZE
(CQJX) 0.375 INCHES
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT
(CQWN) 0.055 MINIMUM AT 200 PCT ALL LOCATIONS AND 0.950 MAXIMUM AT 200 PCT ALL LOCATIONS AND 0.240 MAXIMUM AT 400 PCT ALL LOCATIONS
BODY LENGTH
(ADAQ) 1.562 INCHES MAXIMUM
RESET METHOD
(CPRQ) MANUAL
THREAD SERIES DESIGNATOR
(THSD) UNEF
ULTIMATE TRIP TIME PER POLE IN SECONDS
(CPRP) 0.200 MINIMUM ALL LOCATIONS AND 7.000 MAXIMUM ALL LOCATIONS
TEST DATA DOCUMENT
(TEST) 81349-MIL-C-39019 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
MANUAL ACTUATOR TYPE AND QUANTITY
(CPRT) 1 TOGGLE
TERMINAL TYPE AND QUANTITY
(TTQY) 4 WIRE HOOK

Manufacturer Part Numbers


Related Inventory

MILC39019-3
5925001114756