CIRCUIT BREAKER

Federal Supply Classification
FSC 5925 - Circuit Breakers
National Item Identification Number
NIIN 017003491
Codification Country
United States
Item Name Code
INC 00136
Criticality
(X) This item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Hazardous Material Indicator Code
(P) There is no information in the HMIRS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Availability: Request Qualified Suppliers: Currently qualifying suppliers

Manufacture or supply this part?
Join our growing community of certified suppliers.

Let Us Know
  CALL ABOUT NSN 5925-01-700-3491
Our client representatives are standing by to help fulfill your request.

+1-321-773-5710

  REQUEST QUOTE for 5925-01-700-3491


Have a list that needs to be quoted? Upload it here.

DLMS® Summary

National Stock Number 5925-01-700-3491

National Stock Number (NSN) 5925-01-700-3491, or NIIN 017003491, (circuit breaker) was assigned March 24, 2022 in the Federal Logistics Information System (FLIS). This NIIN is Available for Manual Assignment. This NSN does not replace any other NSNs.

There are 3 manufacturer part numbers associated with this NSN. None of the associated part number(s) are considered obsolete. The manufacturer part numbers were originally supplied by 3 suppliers. Today, 3 suppliers are listed as Active suppliers for this NSN. Of the active suppliers, 3 suppliers are deemed design controlled or valid supply parts.

This part number has not been procured by the US Government in over 5 years.

This NSN is assigned to Item Name Code (INC) 00136. [A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES:CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.]. This item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. There is no information in the HMIRS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product. NSN 5925017003491 does not contain precious metals.

This NSN is associated to Schedule B 8536200040: automatic circuit breakers, for a voltage not exceeding 1,000 v, nesoi. The Schedule B End Use is listed as electric apparatus. NAICS classification category 335313: switchgear and switchboard apparatus manufacturing.

This information was last updated on .


Technical Characteristics

CASE MATERIAL
(CWJK) PLASTIC
ACTUATOR FUNCTION
(CPRW) TRIP-RESET
ACTUATOR POSITION DESIGNATION
(CPRX) AT EACH POLE
AUXILIARY SWITCH FUNCTION AND QUANTITY
(CPRZ) 1 ALARM
AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS
(CPRK) 277.0 AC MINIMUM AND 480.0 AC MAXIMUM ALL LOCATIONS
BODY HEIGHT
(ADAU) 50.02 MILLIMETERS MINIMUM AND 51.54 MILLIMETERS MAXIMUM
BODY LENGTH
(ADAQ) 62.86 MILLIMETERS MINIMUM AND 63.62 MILLIMETERS MAXIMUM
BODY STYLE
(AAQL) MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH
(ADAT) 57.53 MILLIMETERS MAXIMUM
BOSS HEIGHT
(AJEC) 3.18 MILLIMETERS MINIMUM AND 3.94 MILLIMETERS MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH
(AEBQ) 18.67 MILLIMETERS MINIMUM AND 19.43 MILLIMETERS MAXIMUM
CIRCUIT PROTECTION TYPE
(CPRH) OVERCURRENT ALL LOCATIONS
END ITEM IDENTIFICATION
(AGAV) RADAR M/BA
FEATURES PROVIDED
(CBBL) ROHS DIRECTIVE COMPLIANCE AND TRIP INDICATOR
FREQUENCY IN HERTZ
(FREQ) 60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED
(CQXF) MOISTURE RESISTANT AND SALT SPRAY PROOF
INTERNAL TRIP RELEASE CONFIGURATION
(CPSM) RELAY TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE
(CPRR) TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY
(CPRT) 3 TOGGLE
OVERALL HEIGHT
(ABKW) 82.89 MILLIMETERS MINIMUM AND 86.95 MILLIMETERS MAXIMUM
OVERALL LENGTH
(ABHP) 62.86 MILLIMETERS MINIMUM AND 63.62 MILLIMETERS MAXIMUM
OVERALL WIDTH
(ABMK) 57.53 MILLIMETERS MAXIMUM
PART NAME ASSIGNED BY CONTROLLING AGENCY
(CXCY) HYDRAULIC MAGNETIC CIRCUIT PROTECTOR
MATERIAL
(MATT) PLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE
(CPLM) 15.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS
(CPRG) 15.0 AC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS
(CPRF) 277.0 AC AND 480.0 AC ALL LOCATIONS
POLE QUANTITY
(AKPX) 3
RESET METHOD
(CPRQ) MANUAL
SPECIAL FEATURES
(FEAT) ONE HANDLE PER POLE. STUD TERMINALS. THREE POLES. AUXILIARY SWITCH, 0.110 QUICK CONNECT, AUXILIARY CONNECTORS REVERSED. 50/60 HZ LONG DELAY. 15 AMP. METRIC THREAD MOUNTING INSERTS AND TERMINALS. 277/480 VAC (50/60 HZ). BLACK. AMBIENT OPERATION TEMPERATURES BETWEEN -40 C TO +85 C. INSULATION RESISTANCE: NOT LESS THAN 100 MEGOHMS AT 500 VOLTS DC. MOISTURE RESISTANCE: MEET ALL THE REQUIREMENTS OF MIL-PRF-55629 WHEN TESTED IN ACCORDANCE WITH METHOD 106 OF MIL-STD-202. SHOCK: CIRCUIT PROTECTORS SHALL NOT TRIP WHEN TESTED PER MIL-STD-202, METHOD 213, TEST CONDITION I WITH 100 PCT RATED CURRENT APPLIED TO DELAYED UNITS AND 80 PCT RATED CURRENT TO INSTANTANEOUS UNITS. VIBRATION: CIRCUIT PROTECTORS SHALL NOT TRIP WHEN VIBRATED PER MIL-STD-202, METHOD 204, TEST CONDITION A WITH 100 PCT RATED CURRENT APPLIED TO DELAYED UNITS AND 80 PCT RATED CURRENT TO INSTANTANEOUS UNITS.
SWITCH CONTACT ARRANGEMENT
(AEGJ) DOUBLE POLE, SINGLE THROW, NORMALLY OPEN AND DOUBLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS
(CSSX) 15.0 AC
SWITCH TERMINAL TYPE
(CRTK) SCREW AND QUICK DISCONNECT, MALE
SWITCH VOLTAGE RATING AND TYPE IN VOLTS
(CSWP) 277.0 AC AND 480.0 AC
TERMINAL TYPE AND QUANTITY
(TTQY) 6 SCREW AND 3 QUICK DISCONNECT, MALE
TRIP RELEASE AMBIENT TEMP RATING
(CRCF) 25.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC
(CPRL) TIME DELAY ALL LOCATIONS
TRIP RELEASE DUTY CYCLE
(CQQC) CONTINUOUS ALL LOCATIONS
TRIP RELEASE METHOD
(CPRJ) MAGNETIC-HYDRAULIC ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT
(CQWN) 6.0 MINIMUM AT 150 PCT AND 60.0 MAXIMUM AT 150 PCT ALL LOCATIONS
UNPACKAGED UNIT WEIGHT
(CTJS) 270.0 GRAMS NOMINAL
TRIP RELEASE AMBIENT TEMP RATING
(CRCF) 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS